根據《供(gong)熱通(tong)(tong)(tong)(tong)風(feng)(feng)設計(ji)手冊》規范GBJ19-87和《DB42實驗(yan)室(shi)通(tong)(tong)(tong)(tong)風(feng)(feng)系統(tong)設計(ji)與施工規范》的相關規定,確定通(tong)(tong)(tong)(tong)風(feng)(feng)柜、消化(hua)柜、原子吸(xi)收(shou)罩等(deng)通(tong)(tong)(tong)(tong)風(feng)(feng)設備、室(shi)內(nei)全面通(tong)(tong)(tong)(tong)風(feng)(feng)換氣(qi)的通(tong)(tong)(tong)(tong)風(feng)(feng)量:
1) 設計中,按室內余熱、余濕(shi)、保(bao)證(zheng)室內衛生條件的最小(xiao)換氣量進行計算。
一般性化學實驗室的通(tong)風量(liang): 10-12次/小時
毒氣室、有機合成、菌(jun)種(zhong)培養的通風(feng)量(liang):15-20次/小(xiao)時
2) 通(tong)風(feng)(feng)(feng)柜(罩)排風(feng)(feng)(feng)工(gong)作面必(bi)須保(bao)持(chi)負(fu)壓(ya)狀態,通(tong)風(feng)(feng)(feng)柜面風(feng)(feng)(feng)速:
VAV狀態 0.5m/s±0.1m/s或根(gen)據用(yong)戶要(yao)求設定其它值。
手動狀(zhuang)態0.3m/s~1m/s,視(shi)窗的高低不(bu)影響面所(suo)設定風速;
3) 通風系統使用終端(duan)噪(zao)音≤55dB ,通風柜面換氣次(ci)數:不小(xiao)于15次(ci);
4) 主(zhu)風管設計風速(su)小于9-12m/s,支風管設計風速(su)小于5-7m/s
5) 排風量:通風柜1500m3/h;
6) 快速執行器響應時間≤1s。
二、 通風機系統機系統規定要求1) VAV變風量變頻調(diao)節(jie)控制,保(bao)證系統多個(ge)通風柜(罩)同時運行時,各(ge)自獨立調(diao)節(jie),不相互干擾。
2) 實驗室(shi)內氣流組織良好(hao),氣流速度及(ji)紊(wen)流度均能控制在較小的范圍內,以免室(shi)內氣體的擾動引起排毒柜(ju)內氣體外溢(yi)。
3) 應有不(bu)同型號和規格(ge)的圓形(xing)或矩形(xing)單個變風量(liang)閥,滿足不(bu)同風量(liang)要(yao)求并與(yu)設計圖紙相符(fu)合;
4) 結合(he)實(shi)驗室排風(feng)控(kong)制系統,包括(kuo)變風(feng)量閥、消音器等能提供實(shi)驗室通風(feng)控(kong)制的完(wan)整解決方(fang)案。
5) 實驗(yan)室(shi)風管在選擇防(fang)(fang)腐蝕較好,硬度高的材質(zhi)。本工(gong)程涉及到所(suo)有風管均可(ke)采用防(fang)(fang)腐蝕性能好的PVC/UPVC材質(zhi),風機全部為腐蝕性能好的玻璃鋼風機。
6) 控(kong)(kong)制(zhi)(zhi)面板為漢字顯(xian)示(shi),可顯(xian)示(shi)通風(feng)(feng)系統(tong)運行時的多項信息。自動與(yu)手動多種工作模式可兼容設定,控(kong)(kong)制(zhi)(zhi)插座電源及照(zhao)明(ming)的開啟,可調節風(feng)(feng)閥角度。
7) 實驗室內(nei)氣流(liu)(liu)組織良好,送回風氣流(liu)(liu)速度(du)及紊流(liu)(liu)度(du)均能控制在較小(xiao)的(de)范(fan)圍內(nei),以免室內(nei)氣體的(de)擾(rao)動引起排(pai)毒(du)柜(ju)內(nei)氣體外溢。